Heat recovery system (integral to unit)Fully closed single primary water circuit
Exhaust gas heat exchanger in primary circuit
PHE between primary and secondary circuits
Auto heat output modulation
Auto heat rejection through vent fan
On-board computer control, protection and monitoring
Engine stop/start, synchronising, modulation
Mechanical, electrical and thermal protection
Optional communication between unit and ENER·G Head Office
Gas / fire detection systems
Heat and gas metering
Export control panel
Fuel Type Natural Gas Electrical output 3.87kWe 1 Heat output 8.38kWh Fuel input LHV 14.5 kWg 2 Gas Pressure 20mbar Hot water flow rate 24.3 L/min 3 Heating water temperature in/out 60°C / 65°C 4 Min methane no of gas 80 Width 1,100mm Depth 570mm Height 1,555mm Weight (operating) 410kg Enclosure Standard External (IP44)
Fuel - reciprocating Yanmar CP4 Combustion cycle 4 stroke spark ignition Cylinders 3 in line Speed 2,000 rpm Aspiration Natural Acoustic enclosure 53 dBA @ 1m std
Type HF Inverter Frequency 50Hz single phase Voltage / PF 230V / 0.97 Full load current 16 A Efficiency 84.5%